Brainboxes PX-246 Spécifications Page 27

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 74
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 26
Installation
Part No. 057-120 8660 OPERATING MANUAL ISSUE 1 07/05/2010 ADM
27
4 INSTALLATION
The DSE8600 Series module is designed to be mounted on the panel fascia. For dimension and mounting details,
see the section entitled Specification, Dimension and mounting elsewhere in this document.
4.1 TERMINAL DESCRIPTION
4.1.1 DC SUPPLY, FUEL AND START OUTPUTS
Icon PIN
No
DESCRIPTION CABLE
SIZE
NOTES
1
DC Plant Supply Input
(Negative)
2.5m
AWG 13
2
DC Plant Supply Input
(Positive)
2.5 mm²
AWG 13
(Recommended Maximum Fuse 15A anti-surge)
Supplies the module (2A anti-surge requirement) and Output
relays E,F,G & H
3 Not Connected
4 Not Connected
5 Not Connected
6 Not Connected
7 Functional Earth
2.5m
AWG 13
Connect to a good clean earth point.
8 Output relay E
1.0m
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
9 Output relay F
1.0m
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
10 Output relay G
1.0m
AWG 18
Plant Supply Positive. from terminal 2. 3 Amp rated.
11 Output relay H
1.0m
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
12 Output relay I
1.0m
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
13 Output relay J
1.0m
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
NOTE:- Terminal 14 is not fitted to the DSE8600 series controller.
Vue de la page 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 73 74

Commentaires sur ces manuels

Pas de commentaire