Front Panel Configuration
Part No. 057-120 8660 OPERATING MANUAL ISSUE 1 07/05/2010 ADM
61
7.2 WARNINGS
Warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to
draw the operators attention to an undesirable condition.
In the event of an alarm the LCD will jump to the alarms page, and scroll through all active warnings and shutdowns.
By default, warning alarms are self-resetting when the fault condition is removed. However enabling ‘all warnings are
latched’ will cause warning alarms to latch until reset manually. This is enabled using the 8600 series configuration
suite in conjunction with a compatible PC.
Display Reason
BATTERY UNDER
VOLTAGE
The DC supply has fallen below the low volts setting level for the duration of the low
battery volts timer
BATTERY OVER VOLTAGE The DC supply has risen above the high volts setting level for the duration of the
high battery volts timer
AUXILIARY INPUTS Auxiliary inputs can be user configured and will display the message as written by
the user.
kW OVERLOAD The measured Total kW is above the setting of the kW overload warning alarm