Front Panel Configuration
66
Part No. 057-120 8660 OPERATING MANUAL ISSUE 1 07/05/2010 ADM
7.6.2 ADJUSTABLE PARAMETERS
Front Panel Configuration Editor
Section Parameter as shown on display Factory Settings
Display
Contrast 53%
Language English, others.
Current Date and Time
hh:mm
Timers
LCD Page Timer 5m
Scroll Delay
2s
ss
s
Battery Under Voltage Warning Delay 1m
Battery Over Voltage Warning Delay 1m
Start Delay Off Load 5s
Start Delay On Load 5s
Start Delay Telemetry 5s
Start Delay Mains Fail 5s
Mains Transient Delay 2s
Return Delay 30s
Mains Transient Time 0.7s
Mains
Under Voltage Trip 184V
Over Voltage Trip 276V
Under Frequency Trip 45Hz
Over Frequency Trip 55Hz
CT Primary 600A
CT Secondary 5A
Mains KW Rating 345kW
Mains KVar Rating 258kW
AC System 3 Phase 4 Wire
Bus
Start Delay On Load 5s
Insufficient Capacity Delay 1s
Battery Under Volts Warning Active
Battery Under Volts Warning Delay 1m
Battery Under Volts Warning 10V
Battery Over Volts Warning Active
Battery Over Volts Warning Delay 1m
Battery Over Volts Warning 30V
Load Level For More Sets 80%
Load Level For Less Sets 70%
Load Ramp Rate 3%/s
Schedule
Scheduler Inactive
Schedule Loading On Load
Inactive (Only Available When
Scheduler Is Active)
Schedule Period
Weekly (Only Available When
Scheduler Is Active)
Schedule Time & Date Selection (1-16)
Press to begin editing then
or when selecting the different
parameters in the scheduler.