Controls and Indications
Part No. 057-120 8660 OPERATING MANUAL ISSUE 1 07/05/2010 ADM
51
5.4 VIEWING THE EVENT LOG
The DSE8600 series modules maintain a log of past alarms and/or selected status changes.
The log size has been increased in the module over past module updates and is always subject to change. At the
time of writing, the 86xx series log is capable of storing the last 250 log entries.
Under default factory settings, the event log only includes shutdown and electrical trip alarms logged (The event
log does not contain Warning alarms), however this is configurable by the system designer using the DSE
Configuration Suite software.
Once the log is full, any subsequent shutdown alarms will overwrite the oldest entry in the log.
Hence, the log will always contain the most recent shutdown alarms.
The module logs the alarm, along with the date and time of the event
If the module is configured and connected to send SMS text, a text of the event is sent also.
To view the event log, repeatedly press the next page button until the LCD screen displays the Event log :
Event log 1
Oil Pressure Low
Shutdown
12 Sep 2007, 08:25:46
Press down
to view the next most recent shutdown alarm:
Continuing to press down
cycles through the past alarms after which the display shows the most recent
alarm and the cycle begins again.
To exit the event log and return to viewing the instruments, press the next page button to select the next
instrumentation page.
Example showing the
possible configuration of the
DSE8600 series event log
(DSE Configuration Suite
Software)
This also shows the factory
settings of the module (Only
shutdown alarms and the
mains status are logged).
This is event 1.